Permit Number: T03CM02547
Parcel: 14027071A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02547
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/05/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q Where is this crane placed in the building? Provide a floor plan that locates this crane and demonstrates that its placement does not affect the adjacent structure systems or building egress.

STRUCTURAL:

q Provide a connection detail for the connection of the wide flange beam to the tube steel columns. Is it simply a bolt through connection from the column top plate to the bottom of the wide flange? Please provide.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q Does this crane have a motor? If it does then either provide the electrical plans for this project or provide a note on the plans that the electrical installation to operate this crane will be submitted under a separate permit. If it does not then indicate on the plans that this is a non-motorized crane.

-End of Review-
06/06/2003 EROSE1 ENGINEERING REVIEW Needs Review
06/06/2003 EROSE1 WWM REVIEW Needs Review
06/06/2003 ELAINE ROSE ZONING REVIEW Needs Review
06/06/2003 EROSE1 FIRE REVIEW Needs Review
06/06/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/06/2003 ELAINE ROSE OUT TO CUSTOMER Completed