Permit Number: T03CM02541
Parcel: 13609020E

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM02541
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2003 SEPTIC APPROVAL WWM REVIEW Approved
08/18/2003 David Thomas BUILDING-RESIDENTIAL REVIEW Denied The foundation calculations for the identified project do not match the size shown for the garage on the site plan and metal building drawings.

Select an Engineer of Record and have the engineer match the building and foundation plans and calculations.
08/18/2003 David Thomas BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM02541

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

STRUCTURAL PLANS:

1. SHOW ALL HEADER SIZES AND MATERIAL.
2. SHOW PRESCRIPTIVE INLINE FRAMING FOR ALL BEARING WALLS
3. GIVE GAUGEING OF METAL FRAMING MEMBERS
4. SPECIAL INSPECTION REQUIRED FOR HIGH STRENGTH BOLTING


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE THOMAS@ 791-5550 EXT. 2208


FOLLOWING COMMENTS ARE FOR STEEL STORAGE BUILDING The foundation calculations for the identified project do not match the size shown for the garage on the site plan and metal building drawings.

Select an Engineer of Record and have the engineer match the building and foundation plans and calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/02/2003 DELMA ROBEY OUT TO CUSTOMER Completed