Permit Number: T03CM02541
Parcel: 13609020E

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM02541
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2003 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM02541

6/23/03 10530 E. OLD SPANISH TRAIL



PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, MODEL ENERGY AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2000 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

3. ALL ENGINEERS AND ARCHITECTS INVOLVED IN THE DESIGN OF THE STRUCTURE ARE TO SEAL THE
RELATED SHEETS OF PLANS, DETAILS AND CALCULATIONS. THIS IS IN ACCORDANCE WITH THE RULES OF
THE STATE BOARD OF TECHNICAL REGISTRATION.

SITE PLAN:

1. PLEASE LOCATE THE WATER METER , SPECIFY THE SIZE, AND SHOW THE WATER SERVICE LINE.

FLOOR PLANS:

1. A2, NOTE #5, PLEASE CLARIFY " 4" CORE X 9" WIDE ". ECO-BLOCK IS A FLAT I.C.F. SYSTEM.

2. A2, NOTE #6, PROVIDE GAUGE OF STUDS.

3. A3, PLEASE LABLE THE WINDOWS WITHIN A 24" ARC OF THE DOOR EDGE (R308.4 ITEM 5) AS SAFETY GLASS.

4. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

STRUCTURAL PLANS:

1. SPECIFY LUMBER GRADE AND SPECIES.

2. PROVIDE MANUFACTURER'S CALCULATIONS AND DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS. ALSO, THE
ENGINEER OF RECORD SHALL REVIEW AND "SHOP DRAWING" STAMP APPROVAL ON TRUSS CALCULATIONS.

3. PLEASE JUSTIFY THE 6X10 BEAMS ON THE PORCHES.


4. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A CROSS SECTION OF THE 48" X 8" CMU WALL AT THE COVERED PORCH.

2. PROVIDE A DETAIL FOR THE INTERIOR PARTITION TO SLAB CONNECTION.

PLUMBING PLANS:

1. PLEASE DOUBLE CHECK THE LENGTH OF THE WATER DISTRIBUTION SYSTEM FROM THE WATER METER TO THE MOST REMOTE PLUMBING FIXTURE AND CONSIDER THE WATER METER SIZE.

ELECTRICAL PLANS:

1. NOTE ON PLANS: ELECTRICAL WORK SHALL COMPLY WITH CHAPTERS 33 - 42, 2000 IRC.

2. TUCSON ELECTRIC'S SR-310 NOTE #10 REQUIRES 2 ½" RISERS FOR 200 AMP SERVICES.

3. THE ISLAND AND THE PENINSULA COUNTER TOPS SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET AT EACH
COUNTER SPACE WITH A LONG DIMENSION OF 24" OR GREATER, AND A SHORT DIMENSION OF 12" OR
GREATER, PER E3801.4.2 AND E3802.4.3.

4. WHERE CEILING FANS ARE SHOWN ON THE PLANS, PROVIDE A NOTE INDICATING ONLY APPROVED
OUTLET BOXES SHALL BE USED, PER E4001.6.

MODEL ENERGY CODE:

1. PROVIDE ENERGY CALCULATIONS PER THE 1998 IECC, OR COMPLY WITH IRC CHAPTER 11.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 791-5550 EXT. 1110
06/26/2003 GERRY KOZIOL WWM REVIEW Denied Applicant called. Septic approved under P03CP03278 - 1250 gallons with 577 leach field.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/27/2003 TAMI ACHONG OUT TO CUSTOMER Completed
06/26/2003 ANGIE SHOFFSTALL REJECT SHELF Completed