Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM02498
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/30/2003 | EROSE1 | WWM | REVIEW | Needs Review | |
| 05/30/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q Provide special inspection certificates for the following items: · Masonry · Field Welding · Epoxy Anchors q Detail 1 on Sheet S3.1 indicates that the lintel steel is to extend 2'-0" past each side of the opening. There is only 1'-4" of masonry past each side of the opening per Sheet S1.1 (10'-0" minus 7'-4" and then divided by 2). Please coordinate. q The same problem described above also exists on one side of the lintel in Detail 11 on Sheet S3.1. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q There are no electrical comments to be addressed. -End of Review- |