Permit Number: T03CM02498
Parcel: 11308012A

Address:
3100 N 1ST AV

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02498
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2003 EROSE1 WWM REVIEW Needs Review
05/30/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q Provide special inspection certificates for the following items:
· Masonry
· Field Welding
· Epoxy Anchors

q Detail 1 on Sheet S3.1 indicates that the lintel steel is to extend 2'-0" past each side of the opening. There is only 1'-4" of masonry past each side of the opening per Sheet S1.1 (10'-0" minus 7'-4" and then divided by 2). Please coordinate.

q The same problem described above also exists on one side of the lintel in Detail 11 on Sheet S3.1.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
05/30/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/30/2003 ELAINE ROSE OUT TO CUSTOMER Completed