Permit Number: T03CM02470
Parcel: 133552300

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM02470
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2003 ROBERT SHERRY WATER REVIEW Approved
06/04/2003 EROSE1 WWM REVIEW Needs Review
06/04/2003 ELAINE ROSE ZONING REVIEW Needs Review
06/04/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:

1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1988 IECC, 1999 NEC codes with local modifications and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan.

2. Please coordinate the parking information on sheet MSP with sheet A0.1. Correct the number of spaces to show the actual number of spaces on Pad 1. Sheet A0.1 shows 93 spaces which requires 4 accessible spaces, one of which shall be van accessible with a minimum 96 inch wide space with a 96 inch wide adjacent access aisle (see Detail 03/SP2) per 2000 IBC, Table 1106.1, Section 1106.4 and ANSI-117.1-1998.

3. Sheet A0.1, Keyed Note #52 is shown on the legend as "Not Used." However, Symbol #52 is used, see redline notes.

4. All exterior light fixtures shall comply with the Tucson/Pima County Outdoor Lighting Code for total lumens per acre and shall be full cut-off shielded.





ARCHITECTURAL COMMENTS:

Sheet A1.1

1. Section reference 2/A2.2b refers to a sheet not in the plans set. Please resolve.

2. Section reference 3/A2.2a is incorrect reference. Please correct.

3. Section reference 3/A2.2 is incorrect. Possibly should be Section 2/A2.2? Please correct.


Sheet A1.2

1. Keyed note #33 is shown to be "Not Used" on the legend; however, the symbol for Keyed Note #33 is used at the drive-thru canopy. Please resolve.


2. See General Comment #4 concerning all exterior light fixtures.

Sheet A1.3

1. There are note references to General Note #12; however, the General Notes on this sheet only number 1 through 9. Please clarify.

Sheet A2.1

1. See General Comment #4 regarding exterior light fixtures and justify the type of fixtures used. Provide cut sheets on the exterior fixtures and Energy Code Calculations to show the lighting energy complies with 1998 IECC.

Sheet A2.2

1. The roof slope shown on Detail 03/A2.2 does not agree with the roof slope shown on the building elevations. Also, clarify where on the building this detail applies.

Sheet A2.3

1. Detail reference 3/A2.2 is the wrong reference. Please resolve.

2. Detail reference 11/AD3 is incorrect, since there is no Detail 11 on Sheet AD3. Please correct.

Sheet A3.1

1. On Interior Elevation #1 there is a reference to Keyed Note #46; however, Keyed Note #46 is not on the legend. Please resolve.




Sheet A4.1

1. At the Pharmacy Details, Keyed Note Symbol #13 is used on Detail #26; however, Keyed Note #13 is shown to be "Not Used" on the legend. Please resolve.

Sheet A4.3

1. Where are the Overhead Door Detail's Keyed Notes legend? Please clarify.

Sheet AD3

1. See General Comments #4 regarding interior light fixtures compliance with the Tucson/Pima County Outdoor lighting code. Provide cut sheets and calcs to show compliance with the allowable lumens per acre and energy usage per the 1998 IECC.



STRUCTURAL COMMENTS:

1. The structural plans, details and calcs have been reviewed and approved.


PLUMBING COMMENTS:

Sheet P2.1

1. See the Fire Code Examiner's comments on Detail 3 and resolve.

2. Detail #2 is titled "Gas Fired Water Heater." Please coordinate with Note #2 on Detail #2 and Sheets P1.1 and P2.2 which all show the water heaters to be electric.


MECHANICAL COMMENTS:

Sheet M2.2

1. Provide calcs for the outside air ventilation required and supplied to show compliance with 2000 IMC Table 403.3.


ELECTRICAL COMMENTS:

Sheet E1.1, E3.1, & E4.1

1. Provide calculations to show the interior lighting and exterior lighting energy complies with 1998 IECC Table 705.4.

2. Provide exterior lighting calcs to show the total lumens per acre and shielding complies with the Tucson/Pima County Outdoor Lighting Code for Pad 1.


Sheet E2.1

1. Please complete Note #9 with the available short circuit current from the electric Utility and the Fault Current calcs for the distribution system.

Sheet E4.3

1. At Detail #8, clarify Keyed Note #21 symbol, since there is no Keyed Note #21 on the legends on this sheet.




ENERGY CODE COMMENTS:

1. The building envelope energy calcs and related plan information has been received and approved.

2. See previous notes regarding both interior and exterior lighting energy usage and provide calcs to verify compliance with 1998 IECC.


ACCESSIBILITY COMMENTS:

1. See earlier comments about the number of parking spaces, including accessible spaces, and resolve.
06/04/2003 EROSE1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2003 ELAINE ROSE OUT TO CUSTOMER Completed