Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2003 EROSE1 WWM REVIEW Needs Review
06/16/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 3
1. The 2650SH window adjacent to the door in the utility room requires safety glazing. Ref. R308.4.5.

2. Please specify wind loading in design criteria as 75 mph fastest mile, 90 mph 3-second gust. Ref. R301.2.1.3.

Sheets 4, 4A
1. Show chimney with height and distance dimensions from building elements. Ref. R1001.6.




STRUCTURAL COMMENTS
Sheet 7
1. Specify post to foundation connection at the carport.

PLUMBING COMMENTS
Sheet 9
1. Specify combustion air provisions for the water heater. Ref. UPC 507.

2. Supply and waste tabulations for supply and waste are per UPC Table 6-3 and 7-5 respectively.

3. Gas btu demand load shows 2 water heaters. One water heater is indicated on the plan. Please clarify.

4. BBQ is shown on the plan but not included in the demand calculations. Revise. Ref. UPC 1217.

5. Coordinate water supply sizing. Ref. UPC 610.Plan shows 1". Notes say ½".

6. The BBQ appears to be the most remote gas outlet. Revise calculations with respect to developed length accordingly. Ref. UPC 1217.

7. Show the missing cleanouts. Ref. UPC 707.4.

8. Specify pressure balance or thermostatic mixing valve at tub / shower locations.

9. Specify venting for the water heater. Ref. UPC 512.

MECHANICAL COMMENTS
Sheet 10
1. Dryer venting is not per UMC Sec 908. Specify governing code and indicate size path and termination.

2. Complete the return air routing.

3. Notes 3, 7, 8 and 10 do not appear to apply to this project. Please delete.

4. Revise note 14 to indicate "and IRC as amended by the City of Tucson."

ELECTRICAL COMMENTS
Sheet 8
1. The electrical load calculations indicate a 2 ½ ton and a 4 ton A/C unit. The actual installation appears to be a 5 ton heat pump. Please clarify.



2. An additional convenience receptacle is required in the living room. See redlines. Ref. R3801.

3. Complete circuit information on the plan. See redlines

4. Bedroom 3, identified as circuit 18, appears to have been mislabeled as circuit 1. See redlines.

5. The panel schedule does not show the Jacuzzi from the load calculations. If this option is provided, bonding and grounding are required. Ref. E4109.

6. The light fixture in the master bath shower must be listed for this location. Ref. E3903.

ENERGY COMMENTS - The energy portion has been reviewed and approved
06/16/2003 EROSE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/16/2003 ELAINE ROSE OUT TO CUSTOMER Completed