Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM02460
Parcel: 10714257A

Address:
4 W GRANT RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02460
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2003 EROSE1 WWM REVIEW Needs Review
05/27/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:

q Review the code references on Sheet T-1, several of them are incorrect. The Uniform Plumbing Code should be the 1994 version with State Amendments, the International Energy Conservation Code should be the 1998 version, and the fire prevention code is the International Fire Code and not the Uniform Fire Code. Please correct.

ARCHITECTURAL:

q The new door to the bathroom when in the open position blocks the rear exit. The problem would be solved if the door opening were moved away from the exit and the hinge reversed to also be away from the exit.

q Keyed note #9 points to a sink, however there is no keyed note #9. Please coordinate.

STRUCTURAL:

q There are no structural comments to be addressed.

MECHANICAL:

q Correct the reference to the 1994 UMC in the HVAC Specifications on Sheet M-1. The reference should be to the SMACNA "HVAC Duct Construction Standards - Metal and Flexible" [2000 IMC Sec. 603.3].

q Please provide information demonstrating that the outdoor air requirement is being met [2000 IMC Table 403.3].

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q Are all of the receptacles on the counter next to the sink GFCI protected? The one receptacle is noted as GFI, while the others are not. The symbol used to show these receptacles is also not in the electrical symbol legend. Please clarify.

-End of Review-
05/27/2003 EROSE1 WATER REVIEW Needs Review
05/27/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2003 ELAINE ROSE OUT TO CUSTOMER Completed