Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-COMMERCIAL
Permit Number - T03CM02437
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/04/2003 | DHERRON1 | WATER | REVIEW | Approved | |
| 09/17/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | Plan review for the above-referenced project has been completed, per the 2000 IBC and IMC, 1998 IECC and ICC/ANSI A117.1, 1999 NEC, with all local amendments and the 1994 UPC with Arizona State Amendments. This letter reflects comments to be addressed with a written response to each of the noted items indicating the action taken. In order to facilitate a shorter back-check time, we request that you please provide revised plans and calculations, highlighting any changes that have been made. SCOPE OF REVIEW: The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q A special inspection certificate is required for concrete on this project [2000 IBC Sec. 1704.4]. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q The plumbing general notes on Sheet MP1 reference that this project is to meet the 2000 International Plumbing Code. The actual requirement is to meet the 1994 Uniform Plumbing Code as amended by the State of Arizona. q Permanent ladder access is required for any water heater mounted on a platform at 8'-0" or higher above the finish floor [1994 UPC Sec. 511.2]. ELECTRICAL: q Indicate the requirements for bonding of the electrical system [1999 NEC Art. 250-104]. Specifically address the water piping and the metal building. -End of Review- If you have any questions, please call (520) 750-7474. |
| 09/17/2003 | DHERRON1 | WWM | REVIEW | Needs Review | |
| 09/17/2003 | DHERRON1 | ZONING | REVIEW | Needs Review | |
| 09/17/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | AT 3RD PARTY OFFICE | Completed | Plan review for the above-referenced project has been completed, per the 2000 IBC and IMC, 1998 IECC and ICC/ANSI A117.1, 1999 NEC, with all local amendments and the 1994 UPC with Arizona State Amendments. This letter reflects comments to be addressed with a written response to each of the noted items indicating the action taken. In order to facilitate a shorter back-check time, we request that you please provide revised plans and calculations, highlighting any changes that have been made. SCOPE OF REVIEW: The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval. GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q A special inspection certificate is required for concrete on this project [2000 IBC Sec. 1704.4]. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q The plumbing general notes on Sheet MP1 reference that this project is to meet the 2000 International Plumbing Code. The actual requirement is to meet the 1994 Uniform Plumbing Code as amended by the State of Arizona. q Permanent ladder access is required for any water heater mounted on a platform at 8'-0" or higher above the finish floor [1994 UPC Sec. 511.2]. ELECTRICAL: q Indicate the requirements for bonding of the electrical system [1999 NEC Art. 250-104]. Specifically address the water piping and the metal building. -End of Review- If you have any questions, please call (520) 750-7474. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/17/2003 | DHERRON1 | OUT TO CUSTOMER | Completed |