Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM02421
Parcel: 10408052D

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM02421
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2003 JIM TATE ENGINEERING REVIEW Approved A copy of the stamped approved Site Plan must be included in the submittal.
05/22/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide access and working space for water heater. Reference Section 511.0 UPC.
2. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994.
3. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 1994.
05/22/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the ventilation calculations. Ventilation calculations for sales areas are based on the actual area being ventilated, not the occupied area. Reference Table 403-3, footnote e, IMC 2000.
2. Ventilation for restrooms in public spaces requires 75 CFM of mechanical exhaust per water closet or urinal. Reference Table 403.3, IMC 2000.
3. Please coordinate the exhaust fan numbers on the floor plan with the schedule. Reference Section 302.3, Uniform Administrative Code 1997.
4. Provide automatic economizers with RTU-3 and RTU-4. Reference Section 703.6, IECC 1998.
05/22/2003 ROBERT SHERRY WATER REVIEW Approved
05/22/2003 JIM EGAN FIRE REVIEW Denied 1. Fire Hydrants required. Submit approved COT Water Plan.
2. Provide complete fire sprinkler system design criteria on plans.
a. Standard to be used.
b. Hazard classification.
c. Minimum design density and area of application.
d. Water Supply Information. Static Psi, Residual Psi and Flow GPM.
05/23/2003 GERRY KOZIOL WWM REVIEW Approved
06/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied
06/16/2003 PETER MCLAUGHLIN ZONING REVIEW Approved An approved dev. plan is required prior to bldg. plan approval.
06/16/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Deferred submittal for steel joist requires approval of the building official. Submit a written request including the approximate time of the submittal.
2. Provide calculations for cantilevered trellis.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/22/2003 LISA LESNY OUT TO CUSTOMER Completed