Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM02421
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/21/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | A copy of the stamped approved Site Plan must be included in the submittal. |
05/22/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide access and working space for water heater. Reference Section 511.0 UPC. 2. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994. 3. Provide cleanouts in the building sewer at intervals not exceeding 100 feet. Reference Section 719.1, UPC 1994. |
05/22/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the ventilation calculations. Ventilation calculations for sales areas are based on the actual area being ventilated, not the occupied area. Reference Table 403-3, footnote e, IMC 2000. 2. Ventilation for restrooms in public spaces requires 75 CFM of mechanical exhaust per water closet or urinal. Reference Table 403.3, IMC 2000. 3. Please coordinate the exhaust fan numbers on the floor plan with the schedule. Reference Section 302.3, Uniform Administrative Code 1997. 4. Provide automatic economizers with RTU-3 and RTU-4. Reference Section 703.6, IECC 1998. |
05/22/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/22/2003 | JIM EGAN | FIRE | REVIEW | Denied | 1. Fire Hydrants required. Submit approved COT Water Plan. 2. Provide complete fire sprinkler system design criteria on plans. a. Standard to be used. b. Hazard classification. c. Minimum design density and area of application. d. Water Supply Information. Static Psi, Residual Psi and Flow GPM. |
05/23/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | |
06/16/2003 | PETER MCLAUGHLIN | ZONING | REVIEW | Approved | An approved dev. plan is required prior to bldg. plan approval. |
06/16/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Deferred submittal for steel joist requires approval of the building official. Submit a written request including the approximate time of the submittal. 2. Provide calculations for cantilevered trellis. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/22/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |