Permit Number: T03CM02343
Parcel: 118031800

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/WWM

Permit Number - T03CM02343
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2003 JIM TATE ENGINEERING REVIEW Approved
05/15/2003 PETER MCLAUGHLIN ZONING REVIEW Approved
05/15/2003 PETER MCLAUGHLIN NPPO REVIEW Passed
05/19/2003 GERRY KOZIOL WWM REVIEW Denied Needs Wastewater credit evaluation, 8th floor, 740-6500
05/29/2003 GP BUILDING-RESIDENTIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet 2
1. Please specify length, diameter and minimum embedment of anchor bolting shown in detail 1/2.

2. Provide interconnected, hardwired smoke alarms with battery back up. Ref. R317.1.1.

Sheet 4
1. Specify horizontal framing members for the bath addition.

2. This sheet references section B/5. No section B drawing appears on Sheet 5. Please provide.


STRUCTURAL COMMENTS
Sheet 4
1. Please specify connections for post to foundation and double top plate to header at the 8' family room opening.

PLUMBING COMMENTS
Sheet 2
1. Specify whirlpool bathtub compliance for access, pump location and circulation piping in accordance with UPC 413.

2. The fixture schedule indicates fixtures to be both new and existing. Please clarify.

3. The water heater in the garage indicates both new and existing. Please clarify.

MECHANICAL COMMENTS
Sheet 2
1. The water heater in the garage does not show combustion air provisions. Please detail. Ref. M1703.

2. The water heater in the garage must have the ignition source elevated at least 18 inches above the floor and be protected from impact. Ref. M1307.3.

ELECTRICAL COMMENTS
Sheet 2
1. Circuit 18, for the whirlpool tub, must have ground fault circuit interrupter protection. Ref. E4109.1.

ENERGY COMMENTS - The energy portion has been reviewed and approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed