Permit Number: T03CM02340
Parcel: 10511061R

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM02340
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A1
1. Specify reference to details on Sheet A8 for the method of attachment for wall types B through H at wall to foundation and wall to structure above conditions. Ref. IBC 1613.

2. Specify door type D4, on the path of egress, to comply with IBC 1003.3.1.8. No keys, special knowledge or effort may be required on the path of egress.

Sheet A6.1
1. The base material in the toilet room must be of nonabsorbent material. Ref. IBC 1209.



PLUMBING COMMENTS - The plumbing portion has been reviewed and approved by the City of Tucson.

MECHANICAL COMMENTS - The mechanical portion has been reviewed and approved by the City of Tucson.

ELECTRICAL COMMENTS
Sheet E-1
1. Circuit L-34 was not found on the plan. Please clarify.

2. Coordinate with energy comment #1.

ENERGY COMMENTS
General
1. Please provide the interior lighting power analysis. Ref. IECC 705.
06/03/2003 EROSE1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/03/2003 ELAINE ROSE OUT TO CUSTOMER Completed