Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM02340
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2003 | GP | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL COMMENTS Sheet A1 1. Specify reference to details on Sheet A8 for the method of attachment for wall types B through H at wall to foundation and wall to structure above conditions. Ref. IBC 1613. 2. Specify door type D4, on the path of egress, to comply with IBC 1003.3.1.8. No keys, special knowledge or effort may be required on the path of egress. Sheet A6.1 1. The base material in the toilet room must be of nonabsorbent material. Ref. IBC 1209. PLUMBING COMMENTS - The plumbing portion has been reviewed and approved by the City of Tucson. MECHANICAL COMMENTS - The mechanical portion has been reviewed and approved by the City of Tucson. ELECTRICAL COMMENTS Sheet E-1 1. Circuit L-34 was not found on the plan. Please clarify. 2. Coordinate with energy comment #1. ENERGY COMMENTS General 1. Please provide the interior lighting power analysis. Ref. IECC 705. |
| 06/03/2003 | EROSE1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |