Permit Number: T03CM02339
Parcel: 10511061C

Address:
4550 N ORACLE RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02339
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2003 EROSE1 WWM REVIEW Needs Review
05/29/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
General
1. Please revise the Drawing Index on Sheet CS-1 to reflect the Electrical Plansheets that are issued for second floor partial remodel (4/24/03)

2. Revise code references in the General Notes on Sheet CS-1 to reflect the 2000 IBC sections where the UBC has been used.

3. Identify on the plans the yearly editions of the IBC, IMC, UPC and NEC governing this project as well as incorporating the data shown on the Code Review Checklist into a Code Data Block.

4. Please clarify the Legend on Sheet CS-1 for the symbol consisting of a line with spaced hash marks denoted as interior partition by OFIXO floor to ceiling as it is not clear if these are new interior partition walls that must comply with IBC Table
601 for type of construction, and required to withstand minimal lateral loads, or if this call out is intended to identify walls that receive some type of display finish that is applied to a typical interior steel stud partition.

5. Identify the materials to be used for interior finishes/wall covering to meet the flame spread and smoke development ratings of IBC Table 803.4, and clarify what is intended to serve as the column enclosures in the legend of wall types where column enclosures by OFIXCO are denoted. Identify and/or delete all unused wall types and unused symbols.

6. The shape of the project area identified on Sheet CS-1 does not appear to match the Key Plan that occurs on other plansheets; please clarify and coordinate.

7. Upper Level Ceiling Plan for Area D appears to be missing; please clarify.

8. Comply with the requirements of IBC 106.1.2 and provide exiting plan showing maximum travel distance, the maximum common path of egress travel location of all exits and the required versus provided width at each location. Ref. IBC Table 1003.2.3, 1003.3.1.3.5, 1003.3.1.8 and 1004.2.1. Identify the locations of interconnections with the Mall.

9. Dimension compliance with IBC 1108.12.3 for Sales Counters.

10. Please address status of compliance with IBC 3408.6 & 3408.7.

Sheet A-5
1. In the vicinity of Stair 2, there are symbols identifying new partitions that occur outside the 2003 limits of work line. Also at Gridlines K-9 on Sheet A-8, similar apparent work beyond the boundary identified as the limits of work is shown; please clarify.

Sheet A-7
1. Please identify what is intended for the diagonal stripped rectangle near Gridline 13-G.

2. Identify all room/area uses. See triangle shaped area in the vicinity of Gridline F-13. Clarify rooms near Grid B off Room 216 on Sheet A-5 similarly.



Sheet A-8
1. Clarify in the Legend on Sheet CS-1 if the concrete block walls such as that shown from Grid L to R along Line 10 are new or existing. Also clarify/coordinate the horizontal striped wall section between Grids N and P along Line 10 as this symbol does not appear in the Legend.

2. Clarify note for locking doors at door from Corridor 264 to Alteration Room 220. Comply with IBC 1003.3.1.8 for type of lock/latch

Sheet A-10
1. Clarify where Door 201 occurs in this plan set and denote hardware compliant with ANSI A117.1 as appropriate.

Sheet A14.1
1. Delete or mark "Void" all unused details for the scope of work under this permit.

2. Provide documentation indicating the attachment of partition walls to the suspended ceiling system such as reflected in Detail B-7 is approved for such use.

Sheet A-28
1. Please show location of all exit signage. Ref. IBC 1003.2.10, 1003.2.10.3 at stairways, 1003.2.11.2 for separate power source at exit discharge locations.

STRUCTURAL COMMENTS - Structural has not been made a part of this review.

PLUMBING COMMENTS - Plumbing has not been made a part of this review.

MECHANICAL COMMENTS-The Mechanical portion has been reviewed and approved.

ELECTRICAL COMMENTS
General
1. Address compliance with IBC 907.2.7 for alarm, including accessibility provisions.
05/29/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed