| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the components required to comply with NFPA 37, sections 5.4.1 and 5.4.4. |
| 08/25/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Ferrous gas piping installed underground must have a machine-applied protective coating. Reference Section 1211.5, UPC, 1994. 2. Manually operated gas valves must comply with Section 1210, UPC, 1994. |