Permit Number: T03CM02331
Parcel: 213320250

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM02331
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide gas plan, including developed length, load, pipe sizing calculations, and materials to be used. Reference Section 302.3, Uniform Administrative Code, 1997.
2. Manually operated gas valves must comply with Section 1210, UPC, 1994.
05/16/2003 GERRY KOZIOL WWM REVIEW Passed
05/16/2003 ROBERT SHERRY WATER REVIEW Passed
05/16/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide information to show that the installation of the gas-fired stationary engine complies with the requirements of NFPA 37. Reference Section 915.2, IMC 2000.
06/04/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approv-Cond
06/12/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2003 ANGIE SHOFFSTALL OUT TO CUSTOMER Completed
06/12/2003 ANGIE SHOFFSTALL REJECT SHELF Completed