Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM02331
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/16/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide gas plan, including developed length, load, pipe sizing calculations, and materials to be used. Reference Section 302.3, Uniform Administrative Code, 1997. 2. Manually operated gas valves must comply with Section 1210, UPC, 1994. |
| 05/16/2003 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 05/16/2003 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 05/16/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the installation of the gas-fired stationary engine complies with the requirements of NFPA 37. Reference Section 915.2, IMC 2000. |
| 06/04/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 06/12/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/25/2003 | ANGIE SHOFFSTALL | OUT TO CUSTOMER | Completed |
| 06/12/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |