Permit Number: T03CM02295
Parcel: 122060130

Address:
4311 E SENECA ST

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM02295
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/29/2003 GP BUILDING-RESIDENTIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A1
1. Please clarify if the landing at the family room exterior door is existing or new. Please provide dimensions. Ref. R312.

2. The 4640 window adjacent to the exterior door in the family room requires safety glazing. Ref. R308.4.5.

3. Provide hard wired, interconnected smoke alarms with battery back up for all sleeping rooms and outside of each sleeping area. Ref. R317.1.1.

4. Specify the nonabsorbent surface finishes at the new shower space. Ref. R307.2.

5. Provide the ICBO report number for the proposed stucco system.


Sheet A2
1. Specify headers for interior openings and at the bearing walls opening between the existing kitchen and the new family room.

2. The 2 x 6 rafters exceed the allowable span. Ref. Table R802.5.

3. Coordinate roof sheathing dimension between notes and details.

4. Indicate the grade and species for framing members. Ref. R602.1.

5. Specify fire blocking for concealed draft spaces. Ref. R602.8.

6. Indicate the method of braced wall construction and provide connection details / specifications. Ref. R602.10.

Sheet A3
1. Provide roof ventilation calculations and indicate the size, type and location of venting. Ref. R806.

2. Show and dimension chimney for the fireplace. Ref. R1001.6.


STRUCTURAL COMMENTS
Sheet (Cover)
1. The engineered truss design must bear the seal of an engineer registered in the state of Arizona. Ref. R802.10.2.


PLUMBING COMMENTS
Sheet P1
1. Gas piping must be sized in accordance with the Uniform Plumbing Code. Ref. UPC 1217.


MECHANICAL COMMENTS
Sheet M1
1. Provide the seasonal energy efficiency rating of the rooftop mechanical unit.


ELECTRICAL COMMENTS
Sheet E1
1. Specify the circuit for the hard wired, interconnected smoke alarms with battery back up. Coordinate with architectural comment 3, Sheet A1.


ENERGY COMMENTS - The energy portion has been reviewed and approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed