Permit Number: T03CM02284
Parcel: 123023060

Review Status: Completed

Review Details: OTHER

Permit Number - T03CM02284
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/19/2003 TERRY STEVENS BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM02284
06/20/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

2. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

SITE PLAN: (NOT REQUIRED FOR MODEL PLANS)

1. INDICATE THE LOCATION OF WATER LINE ON THE PROPERTY, AND WHERE IT ENTERS THE BUILDING. PROVIDE THE LOCATION OF YOUR WATER METER.

FOUNDATION PLANS:

1. ALL FOUNDATION HOLD-DOWNS FOR SHEAR WALLS SHALL BE SPECIFIED AND CORRECTLY LOCATED.
NOTE: PAHD42 HOLD DOWNS CANNOT BE USED WITHIN 8" OF A CORNER AND ACHIEVE 1800 LBS. UPLIFT. A HPAHD22 MEETS THIS REQUIREMENT.

FLOOR PLANS:

1. DESIGNATE THE LOCATIONS OF TEMPERED GLASS PER R308.4.--------REQUIRED AT WINDOWS #12 AND #15 BOTH ARE WITH IN 24" OF A DOOR.

2. PROVIDE ACCESS TO EACH SEPARATE ATTIC AND CRAWL SPACE THAT EXCEEDS 30SF. DESIGNATE
LOCATIONS ON THE DRAWINGS. OPENINGS SHALL NOT BE LESS THAN 22" BY 30". THE ATTIC ACCESS SHALL
PROVIDE A MINIMUM OF 30" OF HEADROOM, AND SHALL BE LOCATED IN A HALLWAY OR READILY
ACCESSIBLE SPACE PER R807.

STRUCTURAL PLANS:

1. ROOF FRAMING PLAN SHOWS WOOD LINTELS SUPPORTING CONCRETE. NOT ALLOWED. CLARIFY.

2. DETAIL GABLE END BRACING CONNECTIONS.

3. SPECIFY AND DETAIL ALL OVER FRAMING. IF SOLID SHEATHING IS USED ON THE LOWER TRUSSES, PROVIDE
MINIMUM OPENINGS OF 22" BY 30" FOR ACCESS AND VENTILATION INTO OVER FRAMED AREAS (>30 S.F.). IF
SOLID SHEATHING IS NOT USED ON LOWER TRUSSES, PROVIDE DETAILS FOR BRACING OF TOP CHORD OF
LOWER TRUSSES.

4. NOTE AND DETAIL TIE STRAPS FRAMING ANCHORS AND JOIST HANGERS BY TYPE, SIZE AND REQUIRED
ATTACHMENT TO FRAMING MEMBERS.

5. HOLD DOWNS REQUIRED AT BOTH ENDS OF A BRACED WALL PANEL ------MISSING AT GARAGE FRONT.

ELEVATIONS:

1. SHOW CALCULATION OF ATTIC VENTILATION AREA IN COMPLIANCE WITH R806.2. NOTE LOCATION OF ALL
VENTS NEEDED TO COMPLY.

PLUMBING PLANS:

1. THE CITY OF TUCSON HAS NOT ADOPTED THE PLUMBING SECTION OF THE IRC 2OOO. THE CURRENT CODE BEING USED IS THE 1994 UPC WITH THE STATE AMENDMENTS. ALL PLANS MUST REFERENCE TO THIS CODE.

2. WATER LINE: PROVIDE TOTAL FIXTURE DEMAND & MAXIMUM DEVELOPED LENGTH FOR ENTIRE HOUSE. MAIN WATER LINE MAY HAVE TO BE CHANGED.


MECHANICAL PLANS:

1. GAS APPLIANCES SHALL COMPLY WITH 1994 UPC WITH STATE AMENDMENTS FOR COMBUSTION AIR REQUIREMENTS. DETAIL HOW.

2. 4" GAS FLUE IS INADEQUATE FOR BOTH WATER HEATER AND FURNACE

ELECTRICAL PLANS:

1. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL
RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL
HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5.

2. NOTE THAT ALL SMOKE DETECTORS MUST BE INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH BATTERY BACKUP.

IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112