Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM02259
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/13/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Termination of the excess pressure relief from the water heater over a mop sink is not approved location. Reference Section 608.5, UPC 1994. 2. Resolve disparities in Water Calculation, Sheet P1.1. Is the system predominantly flush valves or flush tanks? Correct pipe sizing if required. Reference Section 302.3, Uniform Administrative Code 1994 3. Provide size and slope of existing building drain. What is the expected total number of future fixture units to be handled by the building drain? Reference Section 302.3, Uniform Administrative Code 1994. |
05/13/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401, IMC. 2. Provide energy code compliance calculations for the mechanical equipment. Reference Section 302.3, Uniform Administrative Code 1994. 3. Clarify operation of EF-4. Reference Section 302.3, Uniform Administrative Code 1994. |
05/13/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/14/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
05/16/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
06/04/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | Provide clearance around water closets per section 604.3 ANSI 117.1 Note: Lav is not allowed to encroach |
06/09/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT LBUCZYN1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS. 1. On Sheet E2.0, please show disconnect and circuitry for HP-2, in similar fashion to that which was done for HP-1 and HP-3. 2. Sheet E1.0 shows circuitry for a sign and some lighting on Panel B2-12. There is no load on this circuit. It is listed as a spare on the panel schedule. 3. Please increase font size for specifications on Sheet E7.0. Specs are hard to read. We require minimum font size #10, which is a little over 1/8". |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/23/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
06/10/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |