Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T03CM02258
Parcel: 10818716A

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02258
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/27/2003 EROSE1 WWM REVIEW Needs Review
05/27/2003 ELAINE ROSE ZONING REVIEW Needs Review
05/27/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A1.0
1. The occupancy group is described as A-3 in the project information block. The more applicable description of the occupancy group would be A-2. Ref. IBC 303.1.

2. The occupancy load calculation indicates one exit required. The common path of egress travel may not exceed 75 feet. Please address. Ref. IBC 1004.2.5.

Sheet A3.1
1. Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Ref. 1003.3.1.8.

2. Please specify the connection of partition walls at top and bottom. Ref. IBC 1607.13.

Sheet A5.0
1. Permanent access and working space provisions must be shown for the water heater if above ACT specified at 13'-0" A.F.F. Ref. UPC 511.

Sheet A6.2
1. Provide clearance at water closet. Ref. ANSI A117.1, 604.3.

2. Note the coat hook height at 48" A.F.F. Ref. ANSI A117.1, 604.8.5.

Sheet A7.5
1. Detail access and working space for the water heater. Ref. UPC 511.

STRUCTURAL COMMENTS - The structural portion has been reviewed and approved.

PLUMBING COMMENTS
Sheet P1.0
1. In the piping specifications, indicate specifically that PVC piping must be PVC DWV. Ref. UPC 701.

2. Please provide specifications for an expansion tank as shown on sheet P3.0 for the water heater. Ref. UPC 608.3.

3. Specify cross connection control for the P358 hose bibb. Ref. UPC 603

Sheet P3.0
1. Show the cleanouts for the second toilet room. Ref. IMC 403.3.

MECHANICAL COMMENTS
Sheet M2.0
1. Provide mechanical exhaust for second toilet room. Ref. IMC 403.3.

2. Please clarify the keynote suggesting condensate drainage to the toilet rooms. Condensate disposal appears to be handled as indirect waste to the floor sink. Coordinate with HVAC notes which specify mop sink. Ref. UPC 801.

3. Specify condensate disposal provisions for condenser serving ice machine. Ref. IMC 307.2.

ELECTRICAL COMMENTS
Sheet E7.0
1. Circuit 26 on panel 2D1 was not identified on the power plan. Please clarify.

2. Coordinate the location of wiring and sensor for circuit 20, panel 2D1 with mechanical. Ref. IMC 606.



ENERGY COMMENTS
General
1. Please provide the interior lighting power analysis. Ref. IECC Table 705.4.
05/27/2003 EROSE1 WATER REVIEW Needs Review
05/27/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/27/2003 ELAINE ROSE OUT TO CUSTOMER Completed