Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2003 JIM EGAN FIRE REVIEW Approved
05/07/2003 ROBERT SHERRY WATER REVIEW Approved
05/07/2003 ANY BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION.
05/07/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
05/07/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
06/05/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Water pressure calulations must be sealed. Resolve differences between calculations on drawing and calculations submitted on 8-1/2"x11 sheet.
2. Use results of water pressure calculations to size water pipes.
3. Drawing modifications made in pencil are not acceptable.
06/05/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1.Provide ventilation alculations per Section 403, IMC 2000.
2. Relocate exhaust termination to conform to Section 401.5.2, IMC 2000.