Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM02218
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/07/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
05/07/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
05/07/2003 | ANY | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ON APPLICATION. |
05/07/2003 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
05/07/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
06/05/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Water pressure calulations must be sealed. Resolve differences between calculations on drawing and calculations submitted on 8-1/2"x11 sheet. 2. Use results of water pressure calculations to size water pipes. 3. Drawing modifications made in pencil are not acceptable. |
06/05/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1.Provide ventilation alculations per Section 403, IMC 2000. 2. Relocate exhaust termination to conform to Section 401.5.2, IMC 2000. |
06/16/2003 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
06/16/2003 | CAGUILA1 | WWM | REVIEW | Needs Review |