Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM02218
Parcel: 12215215A

Address:
3350 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM02218
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2003 JIM EGAN FIRE REVIEW Approved
05/07/2003 ROBERT SHERRY WATER REVIEW Approved
05/07/2003 ANY BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ON APPLICATION.
05/07/2003 BLANCA ESPINO ENGINEERING REVIEW Approved
05/07/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
06/05/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Water pressure calulations must be sealed. Resolve differences between calculations on drawing and calculations submitted on 8-1/2"x11 sheet.
2. Use results of water pressure calculations to size water pipes.
3. Drawing modifications made in pencil are not acceptable.
06/05/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1.Provide ventilation alculations per Section 403, IMC 2000.
2. Relocate exhaust termination to conform to Section 401.5.2, IMC 2000.
06/16/2003 CAGUILA1 ZONING REVIEW Needs Review
06/16/2003 CAGUILA1 WWM REVIEW Needs Review