| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/11/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | On back of Permit Application. Letter submitted by Architect authorizes a reduction in wire size (feeder to Panel A) from 3/0 Cu to 4/0 Al, which has an ampacity of 180. Fuse in disconnect is 200 AF. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/20/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |