Permit Number: T03CM02166
Parcel: 122184310

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM02166
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2003 JIM TATE ENGINEERING REVIEW Denied Site Plan approval is required prior to building plan approval.
07/29/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2000, for mercantile occupancy.
2. The two-way cleanout detail (201/P-3) is drawn incorrectly. Please revise. Reference Section 707.4 (4), UPC 1994.
3. Increase the minimum slope of the 4" horizontal drainage piping from 1/8"/ft to ΒΌ"/ft unless it is impractical due to the building arrangement or structural features. Reference Sections 708.0 and 718.1, UPC 1994.
08/08/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
08/13/2003 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS

1) Sheet C-2 (Site Plan) No openings are permitted within 5 feet of property line, 5'-10' all openings shall be protected for 1-hr construction. See table 602 and table 704.8 of the IBC 2000.
2) Structural: Sheet S-2, Detail 2 the footing reinforcement called out in calc`s is #5 @ 6" o.c. Plans show #5 @ 12" o.c. Rectify!
3) Sheet A-1 at roof plan shows a tile roof at patio area, however calc`s do not show his. Clarify!
4) Sheet A-4 Re; restroom maneuvering clearance at door of restroom no. 1, 12 inch minimum required. See plan.
5) Structural calc`s./ sheet F-I(FOOTINGS)-Shows a 4 foot sq. footing with # 5 @ 6 inches o.c. ew. -Where is this on plans??
6) Same as 5 above, except, sheet F2---Show where the footing 4'-4"x 4' x 12" w/ # 5 @ 6"o.c. is
used.
7) Provide address as per sec. 501.2 For specifics contact Pima County Addressing phone
740-6480.

8/13/03

1) See comment No. 1 above regarding the opening within the 5'-10'.
08/19/2003 DAN CASTRO ZONING REVIEW Denied Site plan must be approved prior to Zoning Review sign-off.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/20/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
08/20/2003 MONICA VALDEZ REJECT SHELF Completed