Permit Number: T03CM02165
Parcel: 128150790

Address:
5367 E 20TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM02165
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2003 GERRY KOZIOL WWM REVIEW Approved
05/28/2003 GP BUILDING-RESIDENTIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet A.1
1. Clarify if there is an exterior landing for the 6068 SGD on this sheet. Ref. R312.1.2.

Sheet A.2
1. Recheck 2 x 8 #2 Douglas Fir at 24" O.C. for 24' span. Ref. Table R802.5.

Sheet A.3
1. Dimension clearance for water closet in bath 2. Ref. R307.1.

2. Please clarify the nominal wall framing dimension for the plumbing wall at the water closet side of bath 1 and bath 2.

3. A concealed space appears to have been created at the original electric meter and service location. Please specify fire blocking for this area and all horizontal and vertical locations. Ref. R602.8.

Sheet A.4
1. Please specify the nonabsorbent finish materials at the tub / shower combination. Ref. R307.2.

2. Provide the ICBO report # for the zero clearance fireplace. Ref. 1004.1.

3. Dimension the hearth extension and specify the material to be readily distinguishable from the surrounding finish surfaces. Ref. R1004.2.

Sheet A.5
1. Dimension the chimney height. Specify the distance to be maintained for chimney termination. Ref. 1001.b.

2. Please provide the ICBO report # for the stucco system.

Sheet A.7
1. In the exterior wall plate detail 1/A.7, please specify the diameter, length and minimum embedment of the anchor bolts.

2. Specify the post to beam connection in detail 5/A.7.

3. Specify the post to foundation connection in detail. 2/A.7.

STRUCTURAL COMMENTS - The structural portion has been reviewed and approved.

PLUMBING COMMENTS
Sheet A.8
1. Specify ABS or PVC DWV in general plumbing note 10 for material specifications. Ref. UPC 701.1.

2. General note 13 has been repeated as general note 17.

3. Clarify T&PR drain termination. The detail provided conflicts with note 6.

4. Please show branch cleanouts. Ref. UPC 707.4.

MECHANICAL COMMENTS
Sheet A.9
1. Coordinate dryer and washer locations. The mechanical, plumbing, electric and floor plans do not appear to be consistent.

2. Clarify clothes dryer vent termination as through wall or to roof.

ELECTRICAL COMMENTS
Sheet A.10
1. Note smoke alarms to be hard wired, interconnected with battery back up at all sleeping rooms and in the immediate vicinity outside sleeping areas. Ref. R317.

2. Please clarify the location of the panel board.

ENERGY COMMENTS - The energy portion has been reviewed and approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/28/2003 ELAINE ROSE OUT TO CUSTOMER Completed