Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T03CM02092
Parcel: 13348128D

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM02092
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2003 ROBERT SHERRY WATER REVIEW Approved
05/15/2003 EROSE1 WWM REVIEW Needs Review
05/15/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS - The architectural portion has been reviewed and approved.

STRUCTURAL COMMENTS - The structural portion has been reviewed and approved.

PLUMBING COMMENTS
Sheet P1 and P2
1. The 3 compartment sink, and adjacent hand sink appear to be new fixtures but are not listed in the equipment schedule as new or shown in the schematic drawings for supply and waste piping. Please clarify. Coordinate fixture credit evaluation with Pima County Wastewater Management for fixtures to be abandoned with this tenant improvement.

2. No grease interceptor was found in the plumbing drawings. Please clarify if there is an existing or proposed grease interceptor. Ref. UPC 1012 and UPC Appendix H.

MECHANICAL COMMENTS - The mechanical portion has been reviewed and approved.
ELECTRICAL COMMENTS - The electrical portion has been reviewed and approved.

ENERGY COMMENTS - The energy portion has been reviewed and approved.
05/15/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/15/2003 ELAINE ROSE OUT TO CUSTOMER Completed