Permit Number: T03CM02077
Parcel: 12701008A

Review Status: Completed

Review Details: SITE

Permit Number - T03CM02077
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2003 JIM EGAN FIRE REVIEW Approved
05/08/2003 JOE LINVILLE NPPO REVIEW Passed Existing developed site.
05/08/2003 JOE LINVILLE LANDSCAPE REVIEW Denied Revise the landscape plan to match the site plan.
DS 2-05.2.0.X
06/16/2003 DOUG WILLIAMS ENGINEERING REVIEW Denied DATE: June 17, 2003
ACTIVITY NUMBER: T03CM02077
PROJECT NAME: Shell Building at Target Center
PROJECT ADDRESS: 5285 E. Broadway Blvd.
PROJECT REVIEWER: James C. Tate, P.E.

Resubmittal Required: Site Plan

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

1. Show label and dimension the future right-of-way for Broadway. Show label and dimension the future curb. Face of future curb is 12 ft. from the future right-of-way. DS 2-02.2.1.A.19

2. Show label and dimension the existing and future sightr visibility triangles for the driveway ingress/egress from Broadway ( near side is 345 ft. and the far side is 30 ft.) and for the corner of Broadway and Beverly (125 ft. along Broadway, 165 ft. along Beverly). Stem side is 20 ft. See DS 3-01.5.3 and DS 3-01 Figures 16 and 17 for locational requirements.

3. The solid waste enclosure (Detail 5 Sheet A-1) must have side bollards. DS 6-01.4.2.C.2

4. Show the width of the PAAL north of the new structure. DS 2-02.2.1.A.11

5. Label and dimension from street center line (Broadway and Beverly) to existing and proposed curbs and sidewalks. DS 2-02.2.1.A.21

6. Sidewalks are required along both street frontages where the new development is occuring. The sidewalk must be located 3 feet from back of curb. The minimum sidewalk width is 4 feet. DS 3-01.3.3.A DS 3-01.4.1.A.1.a DS 3-01.3.3.A

7. At least one sidewalk must be provided to a project from each street on which the project has frontage. DS 2-08.4.1.A

8. Place a note on the plan that all roof downspouts will be routed under any adjacent sidewalk. Sidewalks must be flood free for up to the ten year event. DS 2-08.4.1.E

9. Show roof drainage. DS 2-02.2.1.A.16

10. Show estimated cut and fill quantities on the plan. DS 2-02.2.1.A.17
06/17/2003 JIM TATE SANITATION REVIEW Denied See Engineering folder comments.
06/17/2003 DAVID RIVERA ZONING REVIEW Denied DSC TRANSMITTAL

FROM: David Rivera FOR: Patricia Gehlen
Senior Planner Principal Planner

PROJECT:

T03CM02077
New Shell Building - Pad "A"
Broadway Boulevard and Beverly Road Transmittal date:

1st Review June 17, 2003

COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. List on the site plan sheet(s) the legal description of the property if the pad has a separate legal description. If the pad is inclusive of the Target property list the legal description of the Target Parcel. DS 2-02.2.1.A.2

2. List on the site plan sheet(s) the project address. DS 2.0.2.1.A.3

3. List the under the location map, the section, township and range in which this site is located. DS 2-02.2.1.A.4

4. Building setback dimensions must be shown on the site plan. The building setback dimension from both Broadway Boulevard and Beverly Road future back of curb locations must be shown. The building setbacks are based on the greatest of 21 feet or the height of the structure. Please dimension as required. DS 2-02.2.1.A.7

5. Dimension the width of the PAAL between the proposed Loading zone location and the parking spaces along the north side of the proposed building.

6. Show graphically on the site plan proposed or existing freestanding signs within the PAD "A" area. The location size and type must be indicated. DS 2-02.2.1.A.

7. List on the site plan the proposed uses (and subject section number) of the new shell building, retail , food service, office etc. DS 2-02.2.1.A.31

6. List the allowed floor area ratio based on the overall lot area. DS 2-02.2.2.A.2

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan
06/17/2003 DAVID RIVERA HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/24/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
06/24/2003 MONICA VALDEZ REJECT SHELF Completed