Permit Number: T03CM02039
Parcel: 10603167C

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03CM02039
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2003 JIM EGAN FIRE REVIEW Approved
05/19/2003 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: May 19, 2003
ACTIVITY NUMBER: T03CM02039
PROJECT NAME: Apollo College
PROJECT ADDRESS: 3550 North Oracle Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. Add the future sight visibility triangles for Oracle and Prince Road. DS 2-02.2.1.A.10.

2. Dimension the one-way Parking Area Access Lane (PAAL) and the PAAL along Windsor Road. If the PAAL along Windsor Street is one-way please label on the site plan. DS 2-02.2.1.A.11.

3. Show drainage patterns and finish grades on the site plan. DS 2-02.2.1.A.16.

4. To determine if this site needs a grading permit cut and fill quantities must be shown on the plan. Provide estimated cut and fill quantities on the site plan. Fill quantities include new asphalt. If fill is over 50 cubic yards please submit a grading permit application with a grading plan with the second site submittal. DS 2-02.2.1.A.17.

5. Show and dimension the future Major Streets and Routes (MS&R) right-of-way for Oracle and Prince Road. DS 2-02.2.1.A.19.

6. Dimension from street centerline to existing and future curbs for Oracle and Prince Road. DS 2-02.2.1.A.21.
05/29/2003 JOE LINVILLE LANDSCAPE REVIEW Denied Submit the previously approved and/or and revised landscape plans. if necessary. DS 2-04.2.0
Submit NPPO Plan or application for exception. LUC 3.8
06/06/2003 DAN CASTRO ZONING REVIEW Approved
06/10/2003 DAN CASTRO HANDICAP-SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/17/2003 CINDY AGUILAR OUT TO CUSTOMER Completed
06/10/2003 ANGIE SHOFFSTALL REJECT SHELF Completed