Review Date Reviewer's Name Type of Review Description Status Comments
09/08/2003 JIM EGAN FIRE REVIEW Denied 1. Provide correct code review checklist. (building does not apprear to be Type 1 construction.
2. Provide complete details on "Concrete Fire Lane". (Minimum thickness of concrete, sub-base, turn radii.)
3. Show location of fire lane and access gates on "Overall Site Plan". Show location and type of emergency ingress device(s). Indicate removal of obstructions to fire apparatus access such as landscaping (low hanging trees) and other items within the required 20 ft. wide, unobstructed width.
09/10/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Please provide all drawings to scale. Reference Section 302.3, Uniform Administrative Code 1997. Third request.
2. Provide dimensions of the overflow scuppers. Reference Appendix D, UPC 1994. Third request.
09/12/2003 Doug Laakso BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.