Permit Review Detail
Review Status: Completed
Review Details: REVISION
Permit Number - T03CM02031
Review Name: REVISION
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/08/2003 | JIM EGAN | FIRE | REVIEW | Denied | 1. Provide correct code review checklist. (building does not apprear to be Type 1 construction. 2. Provide complete details on "Concrete Fire Lane". (Minimum thickness of concrete, sub-base, turn radii.) 3. Show location of fire lane and access gates on "Overall Site Plan". Show location and type of emergency ingress device(s). Indicate removal of obstructions to fire apparatus access such as landscaping (low hanging trees) and other items within the required 20 ft. wide, unobstructed width. |
| 09/10/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Please provide all drawings to scale. Reference Section 302.3, Uniform Administrative Code 1997. Third request. 2. Provide dimensions of the overflow scuppers. Reference Appendix D, UPC 1994. Third request. |
| 09/12/2003 | Doug Laakso | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/18/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 09/18/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |