| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/19/2003 | JIM EGAN | FIRE | REVIEW | Denied | Provide correct code review checklist. Provide area of Admin Bldg and fire rating/opening protectionof exterior walls. 5/19/03 |
| 06/02/2003 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 06/03/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Coordinate the architectural and mechanical building backgrounds. The building shown on the mechanical plans is approximately 2 feet longer than dimensioned on the architectural drawing. Reference Section 302.3, Uniform Administrative Code 1997. 2. Show how the space available for maintenance and access to the heat pump meets the manufacturer's requirement. Reference Section 306.1, IMC 2000. 3. Resolve labeling of the exhaust fans EF-1 and EF-2: EF-2 is not on the Exhaust Fan Schedule and EF-1 is not included in the Sequence of Operation. Reference Section 302.3, Uniform Administrative Code 1997. 4. Provide calculations demonstrating conformance with the requirements of the International Energy Conservation Code, 1998. 5. The discharges of EF-1 and EF-2 are directed into enclosed spaces. Show how this will not violate Section 401.5.2, IMC 2000. |
| 06/03/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Confirm that the materials used in the existing sewer piping are suitable for use under a building. Reference Section 313.4, UPC 1994. 2. Provide access to, or relocate, sewer cleanouts affected by the new building. Reference Section 707.9, UPC 1994. 3. Show how the utility services being covered by the new building will be modified. Reference Section 302.3, Uniform Administrative Code 1997. 4. Provide minimum plumbing facilities for the new building. Reference Section 2902.1, IBC 2000. 5. Provide dimensions of the scuppers and overflow scuppers along with the supporting calculations. Reference Appendix D, UPC 1994. |
| 06/03/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 06/26/2003 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/02/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | SEE COMMENTS ATTACHED TO APPLICATION.DATED 7/7/03. |