Permit Number: T03CM02031
Parcel: 106070980

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM02031
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2003 JIM EGAN FIRE REVIEW Denied Provide correct code review checklist. Provide area of Admin Bldg and fire rating/opening protectionof exterior walls. 5/19/03
06/02/2003 GERRY KOZIOL WWM REVIEW Passed
06/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Coordinate the architectural and mechanical building backgrounds. The building shown on the mechanical plans is approximately 2 feet longer than dimensioned on the architectural drawing. Reference Section 302.3, Uniform Administrative Code 1997.
2. Show how the space available for maintenance and access to the heat pump meets the manufacturer's requirement. Reference Section 306.1, IMC 2000.
3. Resolve labeling of the exhaust fans EF-1 and EF-2: EF-2 is not on the Exhaust Fan Schedule and EF-1 is not included in the Sequence of Operation. Reference Section 302.3, Uniform Administrative Code 1997.
4. Provide calculations demonstrating conformance with the requirements of the International Energy Conservation Code, 1998.
5. The discharges of EF-1 and EF-2 are directed into enclosed spaces. Show how this will not violate Section 401.5.2, IMC 2000.
06/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Confirm that the materials used in the existing sewer piping are suitable for use under a building. Reference Section 313.4, UPC 1994.
2. Provide access to, or relocate, sewer cleanouts affected by the new building. Reference Section 707.9, UPC 1994.
3. Show how the utility services being covered by the new building will be modified. Reference Section 302.3, Uniform Administrative Code 1997.
4. Provide minimum plumbing facilities for the new building. Reference Section 2902.1, IBC 2000.
5. Provide dimensions of the scuppers and overflow scuppers along with the supporting calculations. Reference Appendix D, UPC 1994.
06/03/2003 ROBERT SHERRY WATER REVIEW Approved
06/26/2003 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
07/02/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied SEE COMMENTS ATTACHED TO APPLICATION.DATED 7/7/03.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/08/2003 TAMI ACHONG OUT TO CUSTOMER Completed
07/08/2003 ANGIE SHOFFSTALL REJECT SHELF Completed