Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01998
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2003 ELAINE ROSE ZONING REVIEW Needs Review
05/08/2003 EROSE1 NPPO REVIEW Needs Review
05/08/2003 EROSE1 FIRE REVIEW Needs Review
05/08/2003 GP 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL COMMENTS
Sheet TS1
1. In the code analysis data block, please show the adopted NEC 1999 as the governing electrical code and the 2000 IFC as the governing fire code.

Sheet A1
1. Please specify connection to structure above. Ref. 1607.13.

Sheet A2
1. Elevation 6/A2 of the break 110 elevation and elevation 7/A2 of the lobby 101 coffee bar shows a counter height of 3'-0". The maximum height for this type of installation is 34". Please revise. Refs. IBC 1108.4, ANSI A117.1, 902.3.


STRUCTURAL COMMENTS
General
1. Coordinate with architectural comment 1, Sheet A1. Ref. IBC 1607.13.

PLUMBING COMMENTS
Sheet P1
1. Riser diagram 2/P1 requires clarification of supply line type and sizes to WH, P1 and P3. See redlines. Also, please see plan and water heater detail 3/P3.

2. Ceiling plan indicates a height of 8'-6" for the toilet room. Plan notes on Sheet P1 specify a mounting height below 8'-0". Please coordinate with architectural for dropping ceiling height to accommodate water heater pan with platform and access to equipment. Ref. UPC 511.2.

3. Please show the condensate disposal line specifications, trap and point of termination. Ref. UPC801.

Sheet MP1
General
1. The notes and specifications provided in Section 15300 suggest an automatic fire extinguishing system is to be installed. This information is not consistent with the architectural drawings or the code analysis data shown on Sheet TS1. Please clarify.

MECHANICAL COMMENTS
Sheet M1
1. Please show the provisions for condensate disposal. Ref. IMC306.

ELECTRICAL COMMENTS - The electrical portion has been reviewed and aproved.

ENERGY - The energy portion has been reviewed and approved.
05/08/2003 EROSE1 WWM REVIEW Needs Review
05/08/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2003 ELAINE ROSE OUT TO CUSTOMER Completed