Permit Number: T03CM01952
Parcel: 113110550

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T03CM01952
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2003 MELISSA POULIN WWM REVIEW Approved
12/24/2003 PIMA COUNTY BUILDING-RESIDENTIAL REVIEW Denied Structural:
Sheet a0: concrete notes 1 indicates footings with 3000 psi concrete. 3000 psi concrete requires a special inspection. Provide a special inspection certificate to Pima County Bldg Codes plan review with the upper 2/3rd completed.
In order to complete the structural review provide the structural calculations that accompany the engineers of records seal on sheets a2 and a3.
Questions? Daniel E. Ice , 520-740-6490
Mechanical: City of Tucson subscribes to the 2000 IRC. change any/all uniform code refrences to 2000 IRC references. See mechanical general notes. A 5 ton unit produces a nominal (400 cfm/ton) (5tons) = 2,000 cfm; however, the floor plan diffuser pattern distributes 2,375 cfm. Either make the specified cfm and distributed cfm equal or specify unit output at 2,375 cfm in schedule.
Plumbing: Cold water ingress as shown on site plan and plumbing plan shall agree. Dryer input is 35 cfh in schedule and 65 cfh on floor plan. Please resolve.
Electrical: Comply section 210-52(e), '99 NEC
circuit #27 - comply 210-52(b) '99 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
12/26/2003 TAMI ACHONG OUT TO CUSTOMER Completed
12/24/2003 ANGIE SHOFFSTALL REJECT SHELF Completed