Permit Number - T03CM01913
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2003 David Thomas BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T03CM01913
2ND REVIEW 8/8/03
PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.

FLOOR PLANS:

1. NOTE THAT BATHTUB AND SHOWER ENCLOSURES SHALL BE FINISHED PER p2710 WITH CERAMIC TILE, OR A
LISTED ENCLOSURE, TO A HEIGHT OF 72" ABOVE THE DRAIN PER R702.4 AND R307.2

STRUCTURAL PLANS:

1. PROVIDE CROSS SECTION OF NEW EXTERIOR FRAME WALL

2. INDICATE HEADER SIZES FOR NEW FRAME WALL OVER ALL OPENINGS.

3. COMPLETELY DETAIL ALL CONNECTIONS AND CROSS-REFERENCE TO THE FOUNDATION AND FRAMING
PLANS:
- RAFTERS TO TOP PLATE
- HANGER TYPES
- STRAPS


SECTIONS - DETAILS - MISC. NOTES:

1. PROVIDE A BUILDING CROSS-SECTION. MORE THAN ONE MAY BE REQUIRED TO CLEARLY ILLUSTRATE HOW
THE STRUCTURE IS BUILT.

2. CROSS-SECTIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLAN AND FRAMING PLANS.

MECHANICAL PLANS:

1. INDICATE SIZE AND LOCATION OF COLD AIR RETURN

ELECTRICAL PLANS:

1. IS THE ENTIRE HOUSE BEING REWIRED? IF SO, SEE BELOW. IF NOT INDICATE WHAT IS EXISTING AND WHAT IS NEW.

2. AT LEAST ONE WALL SWITCH CONTROLLED LIGHT OR OUTLET MUST BE PROVIDED IN BATHROOMS,
HALLWAYS, STAIRWAYS, ATTACHED GARAGES, OUTDOOR ENTRANCES OR EXITS AND ALL HABITABLE
ROOMS PER E3801.

3. A RECEPTACLE OUTLET SHALL BE PROVIDED ADJACENT TO THE BASIN IN EACH BATHROOM, PER E3801.6.
BATHROOM OUTLETS SHALL BE ON A SEPARATE 20 AMP CIRCUIT WITH NO OTHER OUTLETS, PER E33603.4.

4. ALL RECEPTACLE OUTLETS IN BATHROOMS, KITCHENS, UNFINISHED BASEMENTS, GARAGES OR CARPORTS,
AT GRADE LEVEL AND WITHIN 6' OF A WET BAR OR KITCHEN SINK SHALL HAVE GROUND FAULT CIRCUIT
INTERRUPTING PROTECTION. NOTE ON THE DRAWINGS AT EACH OUTLET REQUIRING SUCH PROTECTION,
PER E3802.

5. NOTE THAT TWO OR MORE 2OAMP SMALL APPLIANCE CIRCUITS SHALL BE PROVIDED TO SERVE ALL
RECEPTACLE OUTLETS IN THE KITCHEN, BREAKFAST ROOM AND DINING ROOM. SUCH CIRCUITS SHALL
HAVE NO OTHER OUTLETS, PER E3603.2 AND E3801.3-4.5.

6. NOTE THAT AT LEAST ONE 20-AMP BRANCH CIRCUIT SHALL BE INSTALLED TO SERVE THE LAUNDRY ROOM,
AND THIS CIRCUIT SHALL HAVE NO OTHER OUTLETS, PER E33603.3 AND 3801.8.

7. INDICATE THE LOCATION OF ALL AIR CONDITIONING AND HEATING UNITS, AIR HANDLERS, COMPRESSORS
AND DISCONNECTS.

8. NOTE THAT LIGHT FIXTURES IN CLOTHES CLOSETS SHALL BE INSTALLED IN ACCORDANCE WITH E3903.11.

9. SUBMIT PANEL SCHEDULE SHOWING CIRCUIT AMPACITY, WIRE SIZES, PANEL SIZE AND CIRCUIT NUMBERS.

10. SHOW LOCATIONS OF SMOKE DETECTORS PER R317. NOTE THAT ALL SMOKE DETECTORS MUST BE
INTERCONNECTED WITH A POWER SOURCE FROM THE BUILDING WIRING, AND SHALL BE EQUIPPED WITH
BATTERY BACKUP.


IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
TERRY STEVENS @ 791-5550 EXT. 112

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2003 TERRY STEVENS OUT TO CUSTOMER Completed
08/11/2003 ANGIE SHOFFSTALL REJECT SHELF Completed