Permit Number: T03CM01911
Parcel: 110101620

Review Status: Completed

Review Details: 3RD PARTY REVIEW-REVISION/OTHER

Permit Number - T03CM01911
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL REQUIREMENTS:

q Post-it NotesĀ® were left on the vellum set on Sheet 3 when the copy was made. Therefore information was covered up when the second copy was made. Remove the Post-it NotesĀ® and have a new copy made of this Sheet.

ARCHITECTURAL:

q There are no architectural comments to be addressed.

STRUCTURAL:

q Provide a special inspection certificate for the post-tension slab.

PLUMBING PLANS:

q A revised plumbing plan needs to be submitted reflecting the layout of the bathroom and utility room next to bedroom #3, and further showing any revisions to the gas piping layout (does the new fireplace have a log lighter). The reference set submitted shows a different layout for this area.

MECHANICAL PLANS:

q The revised air supply redirected 665 c.f.m. from two registers to two new registers supplying only 420 c.f.m. What happened to the rest to the supply? Please clarify.

ELECTRICAL PLANS:

q There are no electrical comments to be addressed.

ENERGY CODE:

q There are no energy code comments to be addressed.

-End of Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2003 ELAINE ROSE OUT TO CUSTOMER Completed