Permit Review Detail
Review Status: Completed
Review Details: 3RD PARTY REVIEW-REVISION/OTHER
Permit Number - T03CM01911
Review Name: 3RD PARTY REVIEW-REVISION/OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/29/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL REQUIREMENTS: q Post-it NotesĀ® were left on the vellum set on Sheet 3 when the copy was made. Therefore information was covered up when the second copy was made. Remove the Post-it NotesĀ® and have a new copy made of this Sheet. ARCHITECTURAL: q There are no architectural comments to be addressed. STRUCTURAL: q Provide a special inspection certificate for the post-tension slab. PLUMBING PLANS: q A revised plumbing plan needs to be submitted reflecting the layout of the bathroom and utility room next to bedroom #3, and further showing any revisions to the gas piping layout (does the new fireplace have a log lighter). The reference set submitted shows a different layout for this area. MECHANICAL PLANS: q The revised air supply redirected 665 c.f.m. from two registers to two new registers supplying only 420 c.f.m. What happened to the rest to the supply? Please clarify. ELECTRICAL PLANS: q There are no electrical comments to be addressed. ENERGY CODE: q There are no energy code comments to be addressed. -End of Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/29/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |