Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01909
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/22/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:

1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan.

2. Please correct the applicable codes to the 1994 UPC with State Amendments.

ARCHITECTURAL COMMENTS:

Sheet A1.0

1. Correct the occupant load calculation and drop all fractions, since there is no such thing as a fraction of a person.

Sheet A3.1

1. Identify the use of ALL spaces in the tenant space, see redline notes.

STRUCTURAL COMMENTS:

1. No structural changes of note.


PLUMBING COMMENTS:

Sheet P2.0

1. Plumbing Supply Plan Note 15 shows "Not Used"; however, Note 15 symbol is shown in 2 places. Please coordinate and resolve.

MECHANICAL COMMENTS:

Sheet M2.0

1. Revise the Outdoor Ventilation Air Calculations in accordance with 2000 IMC, Table 403.3.

Sheet M3.0

1. Verify the duct insulation and sealing is in accordance with 2000 IMC Section 604 and 1998 IECC, Section 703.8.

ELECTRICAL COMMENTS:

Sheet E1.0

1. Coordinate the applicable code edition with Sheet A1.0 to the 1999 NEC.

Sheet E2.0

1. Coordinate the location of RTU #2 with the Mechanical Plans on Sheet M2.0 and corresponding location of required roof top receptacles.

Sheet E4.0

1. Please explain the "Future term Panel A, Circuits 17 and 18", since the receptacles are shown on the power plan.

ENERGY CODE COMMENTS:

1. Provide lighting energy calculations to verify compliance with 1998 IECC, Table 705.4.

ACCESSIBILITY COMMENTS:

1. The plans have been reviewed and approved for accessibility requirements of 2000 IBC, Chapter 11 and AdA.
04/23/2003 EROSE1 WWM REVIEW Needs Review
04/23/2003 EROSE1 WATER REVIEW Needs Review
04/23/2003 EROSE1 FIRE REVIEW Approved
04/23/2003 EROSE1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/22/2003 ELAINE ROSE OUT TO CUSTOMER Completed