Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2003 Robert Sherry PLUMBING-COMMERCIAL REVIEW Denied 1. Include the demand for all of the existing fixtures (including the hose bibbs) in the demand calculations. Use "private" fixture units when the use of a fixture is limited to an individual or a family; the laundry, kitchen, and the new restroom located off the Living/Recreation area would be "public" fixtures. Not all of the existing fixtures can be considered "private." Confirm the ability of the existing water heaters to supply the new loads. Reference Section 610.3, UPC, 1994.
2. Provide a building shut off valve. Reference Section 605.3, UPC 1994.
3. Modify the pipe sizing to match the provided calculations.
4. Revise notes on sheet P2, that indicate the number of fixture units per zone, to correspond to the correct zones.
08/04/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved