Permit Number: T03CM01904
Parcel: 133553300

Address:
250 S VOZACK LN

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM01904
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/20/2003 GERRY KOZIOL WWM REVIEW Approved
06/26/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Detail 1/P2 contains a prohibited practice; reducing the waste line from 3" to 2" is considered an obstruction. Reference Section 311.5, UPC 1994.
2. Include the demand for all of the existing fixtures in the demand calculations. Use "private" fixture units when the use of a fixture is limited to an individual or a family; the laundry, kitchen, and the new restroom located off the Living/Recreation area would be "public" fixtures. Confirm the ability of the existing water heaters to supply the new loads. Reference Section 202.0, UPC, 1994.
06/26/2003 ROBERT SHERRY WATER REVIEW Passed
06/26/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise minimum outside air amounts on heat pump schedule to agree with the outside air ventilation schedule.
07/08/2003 Martin Haeberle BUILDING-COMMERCIAL REVIEW Approv-Cond
07/16/2003 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/31/2003 TAMI ACHONG OUT TO CUSTOMER Completed
07/21/2003 TAMI ACHONG REJECT SHELF Completed