Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM01904
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/20/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/26/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Detail 1/P2 contains a prohibited practice; reducing the waste line from 3" to 2" is considered an obstruction. Reference Section 311.5, UPC 1994. 2. Include the demand for all of the existing fixtures in the demand calculations. Use "private" fixture units when the use of a fixture is limited to an individual or a family; the laundry, kitchen, and the new restroom located off the Living/Recreation area would be "public" fixtures. Confirm the ability of the existing water heaters to supply the new loads. Reference Section 202.0, UPC, 1994. |
| 06/26/2003 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 06/26/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise minimum outside air amounts on heat pump schedule to agree with the outside air ventilation schedule. |
| 07/08/2003 | Martin Haeberle | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 07/16/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/31/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 07/21/2003 | TAMI ACHONG | REJECT SHELF | Completed |