Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T03CM01904
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/06/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | Zoning 5/6/2003 Copies of the approved development and landscape plans must be included in the submittal package prior to review and approval. |
| 05/13/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Proposed bathrooms do not comply with required clearance requirements for water closets. Reference section 604.3.1 ANSI 117.1. Revise plans. 2. Doors # 9&10 do not comply with maneuvering clearances at doors. Reference section 404.2.4 ANSI 117.1. Revise plans. 3. Laundry room door to be a minimum of 45 min rating. Reference Table 302.1.1 and Table 714.2 IBC. Revise door schedule 4. Indicate required pipe protection on lavs per section 606.6 ANSI 117.1 5. Indicate accessible signage at unisex toilet as per section 1109 ANSI 117.1 6. Ventilation for attic spaces is required per section 1202 IBC. Provide amount, location, and details for the required ventilation. 7. Indicate on plans the required access in concealed spaces for required sprinklers to be provided. 8. Include in structural calculations the impact of the additional loads to the existing roof system. |
| 05/14/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
| 05/15/2003 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
| 05/16/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Condensate from HP-1 terminates in an unapproved location. Reference Section 807.2, UPC 1994. 2. Wet vents are limited to receiving the discharge of 1 and 2 fixture unit fixtures (Detail 1/P2). Reference Section 908.1, UPC 1994. 3. Provide water pressure and pipe sizing calculations. Include the demand for the existing fixtures and the size of the main building water supply. Reference Section 302.3, Uniform Administrative Code, 1997. |
| 05/16/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 05/16/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide smoke dampers at all penetrations of the wall around the laundry room. Reference Section 607.5.4, IMC 2000. 2. Provide information to show that the laundry room complies with Section 504.5, IMC 2000. Reference Section 302.3, Uniform Administrative Code, 1997. 3. Revise minimum outside air amounts on heat pump schedule to agree with the outside air ventilation schedule. 4. Relocate exhaust openings and plumbing vents as required to comply with Section 401.5.1, IMC 2000. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/02/2003 | LISA LESNY | OUT TO CUSTOMER | Completed |
| 05/16/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |