Permit Number: T03CM01898
Parcel: 137060580

Address:
542 W ALASKA ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T03CM01898
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2003 James Tate ENGINEERING REVIEW Denied DATE: August 4, 2003
ACTIVITY NUMBER: T03CM01898
PROJECT NAME: Alex Auto
PROJECT ADDRESS: 542 W. Alaska
PROJECT REVIEWER: James C. Tate, P.E.

Resubmittal Required: Site Plan

This is a Full Code Compliance review.

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

1. Written approval from the Department of Solid Waste Management is required for curbside pickup. Contact John Clark at 791-5414 ext. 1004.

2. The ingress/egress must be a standard driveway apron. See City of Tucson Standard Detail 206 for design requirements. The plan appears to show that this is not a standard driveway apron. It appears that the intention is for cars to enter over the sidewalk. This is not acceptable. Please show a standard driveway apron on the plan.

3. The sight visibility triangle at the corner of Alaska and 12th is incorrect. The length should be 125 ft.

4. The sight visiblity triangles at the egress/ingress on Alaska are incorrect. Switch them. The near side length is 185 ft. (east length). The far side length is 110 ft. (west length).

5. As shown on the supplied documentation the existing right-of-way width for 12th Ave.is 115 ft. However, it has not been shown that it is intended that the centerline of the street be changed. As such, the MS&R half right-of-way width of 50 ft. from street centerline must be shown. Also, show the future curb location and the future sight visibilty triangle. OR Written conformation of your assertion that the street centerline will be changed must be provided from City of Tucson Department of Transportation.

6. Close all curb cuts and depressed curbs which are no longer needed as per Tucson Code Sec. 25.43.
08/04/2003 JIM EGAN FIRE REVIEW Approved
08/26/2003 JOE LINVILLE LANDSCAPE REVIEW Denied 1) The site is subject to LUC 3.7.2.3.A Vehicular Use Areas. Revise the plan to comply.

2) The site is subject to LUC 3.7.2.3.B, Revise the plan to comply.

3) The site is subject to LUC 3.7.2.4.A.3 which requires
that "the area between the right-of-way line and sidewalk
and the area between the sidewalk and the curb, if not covered with vegetation, shall be covered with
an appropriate inorganic ground cover, such as decomposed granite." Revise the plan to comply.

4) The site is subject to LUC 3.7.2.4.A. which requires that "fifty (50) percent or more of the area of the street landscape border must be covered with shrubs or
vegetative ground cover. The required ground coverage must be achieved within two (2) years from the date of planting.
Revise the plan to comply.

5) An interior landscape border per LUC 3.7.2.4.B is required along the east property boundary. Revise the plan to comply.

6) The refuse storage area may not be located within the public right of way, per LUC Table 3.7.2-I the area must be located behind the street landscape borders and screened from adjacent streets. Revise the plans to identify the storage area and provide necessary landscaping and screening.

7) The street landscape border required along 12th Avenue must be located based on the MS&R right of way. Dimensiion the MS&R right of way. LUC 2.8.3.4

8) Per LUC 3.7.3.2.B screens along a street frontage must be located on the development side of the street landscape border so that they do not obstruct the view of the street
landscape border from the street. Revise the plans as necessary.

9) A 5' screen is required along Alaska Street per LUC Table 3.7.2-I, unless the project is "across the street from nonresidential uses or unimproved, nonresidentially zoned parcels" in which case 30" screen may be provided. Include a zoning label for the parcels located across Alaska Street and revise the plans to include the required screening.

10) Existing curb cuts which are no longer used are subject to the provisions of TCC 25-43. Contact Engineering for additional information.

11) Per LUC 3.7.4.5.A "A water-conserving irrigation system is required for all new landscape plantings." Include information on proposed irrigation methods. A plan is required per LUC 3.7.4.5.C.

12) Per LUC 3.7.4.3.B "Grading, hydrology, and landscape structural plans are to be integrated to make maximum use of site storm water runoff for supplemental on-site irrigation purposes. The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area." Revise the plans as necessary.
08/26/2003 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See zoning review comments
08/27/2003 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: R. Bruce Woodruff
2508 E. Seneca
Tucson, AZ 85716
(520) 909-9572

FROM: Peter McLaughlin
Senior Planner
Development Services Dept.

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT: T03CM01898
Alex Auto
542 W. Alaska Street
Change of Use
Site Plan Review (2nd review)

TRANSMITTAL: August 28, 2003


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


1. The building is shown to be in different locations on the site plan drawing (farther from the 12th Avenue curb) and the SVT/drainage plan (farther from the 24' PAAL). Please revise one or the other for consistency and dimension the building on the drawing.
DS 2-02.2.1A.6.

2. The dimension of the sight visibility triangles (SVTs) along 12th Avenue curb is incorrect as shown. Revise to read 125 feet. Also, the lengths of the near-side and far-side SVTs at the access point (along Alaska Street) are reversed. Please revise.
DS 2-02.1.A.10
DS 3-05.2.2.C
DS 3-01.5.1.A.1

3. The minimum print size required for microfilming/archiving purposes is 12 point. The lettering in the SVT & drainage plan does not meet this standard. Please revise.
DS 2-03.2.1.C

4. Remove the notes which read "no outdoor lighting and/or freestanding lighting" and "no billboards shall be permitted on site". Add a statement that the proposed vehicle sales use is subject to LUC 3.5.9.5.A and 3.5.9.5.B.
DS 2-02.2.1.A.31
LUC 2.5.4.2.B.6

5. Revise the last parking note to read "Total provided", instead of "Total Required". The required parking has already been stated in the notes above. DS 2-02.2.2.4

6. Because the proposed location of the bicycle parking is not visible from the 12th Avenue right-of-way, directional signage must be provided to direct bicyclists to the bicycle parking location. Show the location of the directional signage on the drawing. DS 2-09.5.1

7. The van accessible handicapped parking space must have a designated, striped 8' wide access aisle per IBC Sec. 1106.4. Show the location and dimension the striped 8-foot wide access aisle to be provided to serve the van accessible space.
ANSI/IBC

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/04/2003 TAMI ACHONG OUT TO CUSTOMER Completed
08/28/2003 ANGIE SHOFFSTALL REJECT SHELF Completed