Permit Number: T03CM01892
Parcel: 10309074B

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL

Permit Number - T03CM01892
Review Name: 3RD PARTY REVIEW-COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2003 EROSE1 WWM REVIEW Needs Review
08/01/2003 EROSE1 ENGINEERING REVIEW Needs Review
08/01/2003 WILDAN 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL COMMENTS:

1. This project has been reviewed for conformance with the 2000 IBC, 1997 UAC, 2000 IMC, 1998 IECC, 1999 NEC codes with local modifications, and the 1994 UPC with State of Arizona amendments. Any revisions to this plan will require an additional review and approval by Willdan.


ARCHITECTURAL COMMENTS:

Not part of this review.


STRUCTURAL COMMENTS:

Page 3 and 4 of 8

1. The foundation drawing does not identify the allowable soil bearing pressure and requires that the geotechnical engineer for the building soils report confirm the design soil parameters for the proposed tower foundation located 7 feet below grade. Given the close proximity of the existing building, sealed drawings for sheeting, shoring, and bracing are required. Please review and clarify. Reference IBC Sections 106, 1802.6, and 1805.2.2.
2. Signed and sealed foundation design calculations have not been provided. Please provide with your resubmittal. Reference IBC Sections 106 and 1604.4.

3. The design loads shown for the foundation do not appear to have been increased for the essential facility category. Please review and clarify. Reference IBC Section 1604.4.


PLUMBING COMMENTS:

Not part of this review.


MECHANICAL COMMENTS:

Not part of this review.


ELECTRICAL COMMENTS:

Not part of this review.


ENERGY CODE COMMENTS:

Not part of this review.


ACCESSIBILITY COMMENTS:

Not part of this review.





Sincerely,

WILLDAN




Michael J. Brown, C.B.O.
Building Official

MJB/kms

F:\Tucson Office\09058\2003\3133tp02.doc

Documents to be Transmitted Back To Architect, via Airborne Express:

1. 2-copies of Architect's Drawing: Sheet 1 - New Microwave Tower

2. 2-copies of Valmont Design Document Package consisting of:

Tower Calculations
Page 3 with importance factor of 1
2000 IBC Seismic Check
Bill of Materials
Detail Drawings
Insulation Pipe Mount
Mark Antennas, 6-foot, 8 & 10-foot, 4-foot
Drawings Page 1 through 8

3. 2-copies of Geotechnical Report
08/01/2003 ELAINE ROSE ZONING REVIEW Needs Review
08/01/2003 EROSE1 WATER REVIEW Needs Review
08/01/2003 EROSE1 FIRE REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2003 ELAINE ROSE OUT TO CUSTOMER Completed