Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T03CM01880
Parcel: 12907006S

Address:
1585 E 36TH ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T03CM01880
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/02/2003 GERRY KOZIOL WWM REVIEW Approved
07/03/2003 ROBERT SHERRY WATER REVIEW Approved
07/03/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/03/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Correct water pressure calculations; include static lift in the calculations. Resize the piping, RPBP and the water meter as required. Reference Section 302.3, Uniform Administrative Code 1994 and Section 610.2, UPC 1994.
2. Termination of the excess pressure relief from the water heater over a service sink is not approved location. Reference Section 608.5, UPC 1994.
07/17/2003 Doug Williams ENGINEERING REVIEW Approv-Cond Due to recent federal development requirement changes, a Stormwater Pollution Prevention Plan will be required to be submitted and approved with a grading plan/permit application. For details on submittal and content requirements, go to www.adeq.state.az.us/environ/water/permits /stormwater.html.
07/22/2003 David Mann BUILDING-COMMERCIAL REVIEW Approved
07/22/2003 PATRICIA GEHLEN ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2003 LISA LESNY OUT TO CUSTOMER Completed
07/23/2003 ANGIE SHOFFSTALL REJECT SHELF Completed