Permit Number: T03CM01880
Parcel: 12907006S

Address:
1585 E 36TH ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T03CM01880
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/18/2003 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Materials exposed in plenums shall conform to Section 602.2.1, IMC.
2. Modify discharge duct from EF-1 to comply with Section 601.3, IMC.
3. Provide smoke detectors for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC.
4. Provide calculations, size, location and discharge point of scupper for flat roof (see note 2, sheet A4.1 and detail 6, sheet A11.6).
5. Provide updated energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1994.
04/18/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed No changes made since previously approved, 7/25/02
04/21/2003 JIM EGAN FIRE REVIEW Approved
05/15/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
05/16/2003 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T03CM01880 ..1575 E 36TH ST. .. 5/16/03 .. DGL .......... S1) PROVIDE COMPLETED ' CODE REVIEW CHECKLIST ' , SEE WEBSITE FOR FORM. .................. .................. ......... S2) CLARIFY LARERAL ANALYSIS AND DETAILS ON DRAWINGS SHOWING COMPLETE PATH OF LOAD TRANSFER, PARTICULARLY BLOCKING TO PLATE ATTACHED TO STEEL BEAMS.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2003 MONICA VALDEZ OUT TO CUSTOMER Completed
05/16/2003 ANGIE SHOFFSTALL REJECT SHELF Completed