Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T03CM01880
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/18/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Materials exposed in plenums shall conform to Section 602.2.1, IMC. 2. Modify discharge duct from EF-1 to comply with Section 601.3, IMC. 3. Provide smoke detectors for all air distribution systems with a capacity greater than 2,000 CFM. Reference Section 606.1, IMC. 4. Provide calculations, size, location and discharge point of scupper for flat roof (see note 2, sheet A4.1 and detail 6, sheet A11.6). 5. Provide updated energy code compliance calculations. Reference Section 302.3, Uniform Administrative Code 1994. |
04/18/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | No changes made since previously approved, 7/25/02 |
04/21/2003 | JIM EGAN | FIRE | REVIEW | Approved | |
05/15/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
05/16/2003 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T03CM01880 ..1575 E 36TH ST. .. 5/16/03 .. DGL .......... S1) PROVIDE COMPLETED ' CODE REVIEW CHECKLIST ' , SEE WEBSITE FOR FORM. .................. .................. ......... S2) CLARIFY LARERAL ANALYSIS AND DETAILS ON DRAWINGS SHOWING COMPLETE PATH OF LOAD TRANSFER, PARTICULARLY BLOCKING TO PLATE ATTACHED TO STEEL BEAMS. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
06/10/2003 | MONICA VALDEZ | OUT TO CUSTOMER | Completed |
05/16/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |