Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T03CM01878
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2003 | GERRY KOZIOL | WWM | REVIEW | Denied | See previous comments. |
| 10/01/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Resize vent for P-3 and P-2 to comply with Table 7-4 Footnote 3, UPC 1994. 2. Provide vent piping of sufficient size to comply with Section 904.1, UPC. 3. Show size of scuppers on the drawing. (only the height of the scupper is shown on detail 4/A2.4BN). Reference Appendix D, UPC. Note: no provisions for overflows for the roof are evident on the plans. |
| 10/17/2006 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. MPR does not reflect the required fixtures per Table 2902.1 IBC. Note: A total fixture count and occupant load of the school may be used if the total is in compliance with Table 2902.1 IBC. Note: May not use TUSD Enrollment numbers and can only use portion of school within the City of Tucson. Utilize Table 1003.2.2.2 IBC 2. Indicate City of Tucson boundaries on plans, including all property |
| 10/20/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/21/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | see comments under T03CM01875 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 12/04/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |