Permit Number - T03CM01877
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/01/2003 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/01/2003 | Robert Sherry | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Resize vent for P-3 and P-2 to comply with Table 7-4 Footnote 3, UPC 1994. 2. Provide vent piping of sufficient size to comply with Section 904.1, UPC. 3. Show size of scuppers on the drawing. (only the height of the scupper is shown on detail 4/A2.4BN). Reference Appendix D, UPC. Note: no provisions for overflows for the roof are evident on the plans. |
| 10/17/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. MPR does not reflect the required fixtures per Table 2902.1 IBC. Note: A total fixture count and occupant load of the school may be used if the total is in compliance with Table 2902.1 IBC. Note: May not use TUSD Enrollment numbers. Utilize Table 1003.2.2.2 IBC |
| 10/21/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Denied | see comments under T03CM01875 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/08/2003 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 12/04/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |