Review Details: 3RD PARTY REVIEW-COMMERCIAL TI
Permit Number - T03CM01858
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2003 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 04/21/2003 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | GENERAL: q There are no general comments to be addressed. ARCHITECTURAL: q Handrail extensions need to be 12" plus one tread depth beyond the first riser at the bottom of the stairs [ANSI A117.1 1998 - Sec. 505.10.3] (Detail 5 on Sheet A3.0 does not show the additional tread depth extension). STRUCTURAL: q Provide a special inspection certificate(s) for the following: · Engineered Fill · Concrete · Masonry · Welding · Epoxy Anchors MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q There are no electrical comments to be addressed |
| 05/01/2003 | ELAINE ROSE | ZONING | REVIEW | Needs Review | |
| 05/09/2003 | JOE LINVILLE | NPPO | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/01/2003 | ELAINE ROSE | OUT TO CUSTOMER | Completed |