| 05/20/2003 | STANTEC | 3RD PARTY REVIEW-COMMERCIAL | REVIEW | Denied | ARCHITECTURAL: q Sheet A2.1: Proposed alterations to restrooms do not provide compliance with ANSI A117.1-98 as provided in IBC nor ADA. · In the Men's room; the compartment door is in the clear space required for a toilet. Suggest removing the toilet partion. · Both rooms: the toilet paper holder location is not detailed per ANSI A117.1-98 Figure 604.7. The holder location is required to be centered 7-9" to the front of the toilet bowl with bottom at least 15" above the floor and top no higher than 48" max from floor. STRUCTURAL: q There are no mechanical comments to be addressed. MECHANICAL: q There are no mechanical comments to be addressed. PLUMBING: q There are no plumbing comments to be addressed. ELECTRICAL: q Plans indicate there will be electrical alterations. Provide plans. -End of Review- |