Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM01833
Parcel: 127050740

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01833
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2003 ELAINE ROSE ZONING REVIEW Needs Review
05/20/2003 EROSE1 ENGINEERING REVIEW Needs Review
05/20/2003 EROSE1 FIRE REVIEW Needs Review
05/20/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL:
q Sheet A2.1: Proposed alterations to restrooms do not provide compliance with ANSI A117.1-98 as provided in IBC nor ADA.
· In the Men's room; the compartment door is in the clear space required for a toilet. Suggest removing the toilet partion.
· Both rooms: the toilet paper holder location is not detailed per ANSI A117.1-98 Figure 604.7. The holder location is required to be centered 7-9" to the front of the toilet bowl with bottom at least 15" above the floor and top no higher than 48" max from floor.


STRUCTURAL:

q There are no mechanical comments to be addressed.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.


ELECTRICAL:

q Plans indicate there will be electrical alterations. Provide plans.

-End of Review-
05/20/2003 EROSE1 WWM REVIEW Needs Review
05/20/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2003 ELAINE ROSE OUT TO CUSTOMER Completed