Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01833
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2003 ELAINE ROSE ZONING REVIEW Needs Review
05/20/2003 EROSE1 ENGINEERING REVIEW Needs Review
05/20/2003 EROSE1 FIRE REVIEW Needs Review
05/20/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied ARCHITECTURAL:
q Sheet A2.1: Proposed alterations to restrooms do not provide compliance with ANSI A117.1-98 as provided in IBC nor ADA.
· In the Men's room; the compartment door is in the clear space required for a toilet. Suggest removing the toilet partion.
· Both rooms: the toilet paper holder location is not detailed per ANSI A117.1-98 Figure 604.7. The holder location is required to be centered 7-9" to the front of the toilet bowl with bottom at least 15" above the floor and top no higher than 48" max from floor.


STRUCTURAL:

q There are no mechanical comments to be addressed.

MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.


ELECTRICAL:

q Plans indicate there will be electrical alterations. Provide plans.

-End of Review-