Permit Number: T03CM01833
Parcel: 127050740

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01833
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/05/2003 ELAINE ROSE ZONING REVIEW Needs Review
05/05/2003 EROSE1 NPPO REVIEW Needs Review
05/05/2003 EROSE1 FIRE REVIEW Needs Review
05/05/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied GENERAL:
q Remove

ARCHITECTURAL:
q Sheet A2.1: Proposed alterations to restrooms does not provide compliance with ANSI A117.1-98 as provided in IBC nor ADA.
· In the Men's room; the urinal is in the clear space required for a toilet, the lavatory is in the clear space required at the door and the toilet paper holder location is not detailed per ANSI A117.1-98 Figure 604.7.
· In the women's room; the toilet is with in the clear space required at the door and the rear grab bar is not 36" long.
· Neither room indicates location of flush valve handle for the toilets, mirror and towel dispenser heights etc.
q Sheet A2.1: Specify the ICBO or NER for the E.I.F.S. system and specify for installation to comply with the report.

STRUCTURAL:

q The new roof cupola framing needs to be detailed for sheathing shear continuity.
q Provide foundation plan and framing plan for entry arches. Tripple header support is not shown, 3 king studs required per calculations.
q Calculations: wind load per IBC Table 1609.6.2.1(2) should be 90 MPH, exposure B. (Load of 16.5 PSF is OK).
MECHANICAL:

q There are no mechanical comments to be addressed.

PLUMBING:

q There are no plumbing comments to be addressed.



ELECTRICAL:

q Plans indicate there will be electrical alterations. Provide plans.

-End of Review-
05/05/2003 EROSE1 WWM REVIEW Needs Review
05/05/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2003 ELAINE ROSE OUT TO CUSTOMER Completed