Permit Number: T03CM01738
Parcel: 126010020

Review Status: Completed

Review Details: 3RD PARTY REVIEW-COMMERCIAL TI

Permit Number - T03CM01738
Review Name: 3RD PARTY REVIEW-COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2003 STANTEC 3RD PARTY REVIEW-COMMERCIAL REVIEW Denied SCOPE OF REVIEW:

The scope of this review covers Architectural, Structural, Plumbing, Mechanical and Electrical. All features were checked only to the extent allowed by the submittal provided. All portions of the project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL:

q There are no general comments to be addressed.

ARCHITECTURAL:

q There are two detail references on Sheet A-1 where new masonry walls abut old masonry walls, however both references are blank (one refers to a sheet only). Please coordinate.

STRUCTURAL:

q Special Inspection Certificate needs to be provided for the following:
· Masonry
· Field Welding
· Epoxy anchors

q There is a detail reference on the foundation plan on Sheet S-2 to a Detail 12 on Sheet S-4. This detail is blank. Please coordinate. Which detail should be referenced?

q There is a detail reference on the framing plan on Sheet S-3 to a Detail 4 on Sheet S-5. This detail is blank. Please coordinate. Which detail should be referenced?

MECHANICAL:

q The mechanical general notes on Sheet M-1 need to be updated to refer to the 2000 International Mechanical Code, the 2000 International Building Code, and the 1994 Uniform Plumbing Code (as amended by the State of Arizona). The general notes currently reference the Uniform Codes (mechanical, plumbing and building).

q Additional outside air needs to be provided along with the newly addition (through the new mechanical unit). Provide calculation indicating compliance [2000 IMC Table 403.3].

PLUMBING:

q There are no plumbing comments to be addressed.

ELECTRICAL:

q There are no electrical comments to be addressed.

-End of Review-
05/23/2003 ELAINE ROSE ZONING REVIEW Needs Review
05/23/2003 EROSE1 ENGINEERING REVIEW Needs Review
05/23/2003 EROSE1 FIRE REVIEW Needs Review
05/23/2003 EROSE1 WWM REVIEW Needs Review
05/23/2003 EROSE1 WATER REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2003 ELAINE ROSE OUT TO CUSTOMER Completed