Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T03CM01734
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/08/2003 | JIM TATE | ENGINEERING | REVIEW | Approved | |
| 04/15/2003 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 04/21/2003 | PATRICIA GEHLEN | ZONING | REVIEW | Approved | |
| 04/21/2003 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/05/2003 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Structural calculations to be sealed by registrant. 2. Foundation altered to 2' by 2' is adequate. However, calculations call for the use of 3' by 3' footings. Revise calculations 3. Provide beam calculations including point load of girder truss. 4. Submit truss calculations with resubmittal. 5. Provide type of connector to be used for uplift at girder truss/ beam connection. 6. Pin existing footing to new footing. Include note to field verify existing footing as per plan. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/08/2003 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 05/05/2003 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |