Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T03CM01734
Parcel: 110081620

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T03CM01734
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/08/2003 JIM TATE ENGINEERING REVIEW Approved
04/15/2003 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed
04/21/2003 PATRICIA GEHLEN ZONING REVIEW Approved
04/21/2003 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/05/2003 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Denied 1. Structural calculations to be sealed by registrant.
2. Foundation altered to 2' by 2' is adequate. However, calculations call for the use of 3' by 3' footings. Revise calculations
3. Provide beam calculations including point load of girder truss.
4. Submit truss calculations with resubmittal.
5. Provide type of connector to be used for uplift at girder truss/ beam connection.
6. Pin existing footing to new footing. Include note to field verify existing footing as per plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2003 DELMA ROBEY OUT TO CUSTOMER Completed
05/05/2003 ANGIE SHOFFSTALL REJECT SHELF Completed